• 美国德纳科Dynalco SW-200B Speed Switch速度开关

    详细信息

     品牌:Dynalco  型号:SW-200B  加工定制:否  
     适用范围:交通运输,发电,船舶,采矿,水    
    美国德纳科Dynalco SW-200B Speed Switch速度开关

    Download Info:
    SW-200B Data Sheet
    SW-200B Manual
    Product Code: SW-200B

    SW-200B提供可靠的发动机超速保护。它有三个可调继电器设定点:超速。用于两个辅助设备包括曲柄断开,发电机磁场闪烁,和速度监测。设定值是现场可编程的,可以在不超速的情况下进行测试。外壳用垫圈密封。
    The SW-200B provides reliable engine overspeed protection. It has three adjustable relay setpoints: number one is overspeed. Uses for the two auxiliaries include crank disconnect, generator field-flashing, and speed monitoring. Setpoints are field-programmable and can be tested without overspeeding. Housing is gasketed and sealed.

    SW-200B
    Speed Switch

    sw-200btm速度开关提供三个

    发动机可调继电器设定点

    超速保护,曲柄断开,

    发电机磁场闪烁和速度

    全现场编程监控

    能力。
    The SW-200BTM Speed Switch provides three
    adjustable relay set points for engine
    overspeed protection, crank disconnect,
    generator field flashing, and speed
    monitoring with full field-programming
    capability.

    FEATURES
    - Inputs: Senses signal frequency from magnetic
    pickup or AC signal generator.
    - Outputs: Three relays (speed setpoints) and
    one 0-1 mA proportional DC output.
    - Field-programmable: Four DIP switches provide
    a variety of frequency input and overspeed
    relay logic configurations. Also three trim
    potentiometers to adjust setpoint range, and
    one potentiometer to adjust the proportional
    output.
    - Circuit: High-reliability. Virtually immune to
    electrical and RFI noise.
    - Test/Verify: Permits testing without overspeeding.
    - Case: Sealed and gasketed.
    SPECIFICATIONS
    Environment
    - Temperature: (storage & operation)
    –40oF to +185oF (–40oC to +85oC).
    - Vibration:
    - MIL STD 810C, Method 514.2, Curve P,
    Procedure V.
    - MIL STD 202F, Method 201A (10-55 Hz,
    continues displacement of 0.06 in. P-P).
    - Screws on all access holes are predrilled
    for safety wire.
    - Humidity: SAE J1211, paragraph 4.2.3., figure
    3A; 95% relative humidity at +150oF (+66oC).
    - Dust: MIL STD 810C, Method 510.1, Procedure 1,
    Steps 1,4,5,6. (175 ft/min velocity: 0.3 g/ft3 density;
    <176 M average particle size).
    - Sealing: Can open and reseal case without
    damaging watertight integrity. O-ring sealed
    access holes for setpoint and proportional output
    adjustments. Case complies with NEMA Standard
    250, Types 3, 4, 12, and 13.
    - Moisture protection: Component board entirely
    dip-coated with moisture repellent sealant.
    Functional
    Power: 9–40 Vdc, 300 mA maximum.
    Withstands:
    - 800 volts peak reverse voltage.
    - 80 volts peak forward voltage, 0.1
    second maximum duration.
    - 350 volts peak forward voltage, 1 milli-second
    maximum duration.
    Standard signal frequency ranges: 0–11,200, 0–
    5,000, 0–1,000Hz. Field-selectable using built-in DIP
    switches.
    Input Signal:
    - Minimum signal requirement: 50 mVrms
    at frequencies below 1 kHz; 0.4 Vrms at 11
    kHz.
    - Maximum signal: 70 Vrms.
    - Minimum input resistance: 10 kW.

    SPECIFICATIONS

    NOTE
    􀂄 Relays 1 & 2 can be configured as: both
    Normally Open (NO): both Normally Closed
    (NC); or one NC, one NO.
    􀂄 Overspeed relay can be configured as
    normally deenergized (energizes on overspeed).
    CONTACT RATINGS
    - 12 Vdc: 10.0 A, resistive load;
    8.0 A, inductive load.
    - 24 Vdc: 5.0 A, resistive load;
    4.0 A, inductive load.
    - 120 Vac: 0.8 A, resistive or inductive load.
    SETPOINTS
    Resetting: Integral reset push-button switch or by
    momentary removal and reapplication of power.
    Hysteresis (Nominal): 3% for all relays.
    Setpoint adjustment range: 3–100% of full-scale
    frequency range with integral 25-turn trim
    potentiometer for each relay.
    Stability of Setpoints
    - Signal amplitude effect: 0.1% maximum
    from 0.4–100 Vrms.
    - Power Source Effect: 0.1% of setpoint
    maximum with 25% fluctuation of power source.
    - Temperature Effect: 2.5% of selected
    frequency range maximum over operating range.
    Response Time: 50 milliseconds, maximum,
    any setpoint.
    TEST/VERIFY
    Pressing the integral Overspeed Test push button
    lowers the overspeed setpoint to 60% ±3% of its
    original value to permit verifying the integrity of the
    alarm circuitry without overspeeding the engine.
    WEIGHT
    2 lbs (0.9 kg)
    NOTE
    RPM/Frequency Conversion:
    Frequency may be calculated by multiplying the
    engine speed in RPM by the number of holes or teeth
    on the gear/flywheel being sensed, and then dividing
    by 60.
    Grounding, phasing, referencing:
    All circuits are isolated from earth ground. The input
    circuit is referenced to the negative side of the battery
    so that the magnetic pickup can be paralleled with
    electric governors and other devices similarly
    constructed.
    Signal cable shield can be grounded to the negative
    side of the battery.
    DC Power application: At standstill or speeds
    below setpoints, applying dc power causes no flicker
    or change in the normally deenergized relays 1 and 2.
    Tach Output: 0–1 mAdc proportional output for
    speed drives, speed indicators, recorders,
    programmers, etc.
    Field-adjustable to 1 mA full-scale for any frequency
    between 25% and 100% of the selected full-scale
    frequency range.
    - Linearity: 1.5% of selected frequency range.
    - Temperature Effect: 1.5% of selected
    frequency range over the operating range.
    - Signal Amplitude: 0.25% of selected frequency
    range.
    RELAYS
    Comments are for the SW-200B at stand still (poweredup,
    zero speed, no alarms).
    TYPICAL USAGE
    - Standard: One SPDT: Overspeed
    Two SPST: Relays 1 & 2
    - Option: Relays 1 & 2 can be replaced by a
    single SPDT relay.
    Typical Usage
    - Overspeed Relay: Energized. De-energizes
    and latches on overspeed or power loss.
    - Relay 1: Deenergized. Energizes non-latched
    on alarm. Typically used for crank disconnect.
    - Relay 2: Deenergized. Energizes non-latched
    on alarm. Typically used for generator field
    flashing.


    美国德纳科Dynalco控制仪表公司简介

    美国德纳科Dynalco公司设计和制造高度工程坚固,可靠的,第三方的监测,控制和往复式发动机,蒸汽涡轮机,燃气涡轮机,泵和输送系统的保护认证仪表。我们为一个在石油和天然气,化工/过程,建筑业及越野设备,交通运输,发电,船舶,采矿,水和废水市场的客户和工厂自动化等。Dynalco designs and manufactures highly engineered rugged, reliable, 3rd party certified instumentation for monitoring, control and protection of reciprocating engines, steam turbines, gas turbines, pumps and conveying systems. We serve a variety of customers in the Oil and Gas, Chemical/Process, Contruction and off-road equipment, Transportation, Power Generation, Marine, Mining, Water and Waste Water and Factory Automation Markets. 

    Dynalco 1968年创立,有三种产品,以及为石油和天然气工业生产工程解决方案的目标。自那以后的47年里,Dynalco已经成为世界范围内的工业领袖,因其在石油和天然气、化学、电力、海洋和建筑行业使用的高质量的仪器和控制而得到认可。Dynalco was started in 1968, with three products and a goal of producing engineered solutions for the oil and gas industries. In the 47 years since, Dynalco has become a worldwide industry leader, recognized for its high-quality instruments and controls used in the oil & gas, chemical, power, marine and construction industries.

     

    - Dynalco Products

    MTH-103E Tachometer / Hourmeter / Overspeed Trip 
    UM-200 Tachometer / Hourmeter / Monitor 
    Catalyst Monitor 
    UM-600 Universal MonitorInstruments & Controls for Rotating Equipment in 
    Demanding Applications 
    Recently Updated Products M928-24 Magnetic Pickup/Speed Sensor 
    MTH-103D Tachometer / Hourmeter / Overspeed Trip 
    SST-2400H Speed Switch/Transmitter 
    SWTD-1000 Speed Switch/Transmitter
    LMD-120A Panel Meter 
    LMD-120D Panel Meter
    DPM-105 Panel Meter 
    UM-600 Universal Monitor

    Engine Controls & Emissions Controls 
    Instruments/Gauges/Meters 
    - General Purpose Gauges/Meters 
    - Hourmeters 
    - Tachometers 
    - Temperature Gauges/Meters 
    - Universal Scanner Magnetic Pickups/Speed Sensors 
    - Active (Powered) 
    - Cable Assemblies 
    - Extra Long Reach 
    - Hazardous Area 
    - Intrinsically Safe Barriers 
    - Miniature 
    - Power Source 
    - Standard Power Generation 
    Dynalco Speed Switches & Speed Transmitters 
    - DIN Rail and DIN Standard Series 
    - SST Series

    - Dynalco Tachometer转速表

    Dynalco Tachometers转速表型号

    CRT-9x - Replacement Tachometers;The CRT-9X replaces Caterpillar tachometers: CAT-9X114, CAT-9X116, and CAT-9X117. SPD-100 ; SPD-100L ; SPD-108 ; SPD-108L; MTH-103D; F-16; DS-800; DS-900; SPD-700; SPD-708; LST-100; LST-100L; LST-108; LST-100; LST-108L; DST-2000C; PG-100; TT-1; TT-100;DPM-105,LMD-120A,LMD-120,LMD-120D,G-101。

    Dynalco Speed Switch 速度开关型号

    SST-2000A;SST-2000H ;SST-2000A/H;SST-2200A;SST-2400A;SST-2200H;SST-2400H;SW-200B;SW-50;PNT-202

    DYNALCO SST-2000 Series Speed Switches/ Transmitters Product
    SST-2000A Speed Transmitter
    SST-2000H Speed Transmitter
    SST-2200A Speed Switch/Transmitter
    SST-2200H Speed Switch/Transmitter
    SST-2400A Speed Switch/Transmitter
    SST-2400H Speed Switch/Transmitter

    Dynalco Pickup Sensor传感器型号

    M104; M202; M208,M101 ,M102 ,M131,M133 ,M142 ,M151 ,M155 ,M168 ,M183 ,M184,M189 ,M343 ,M801 ,M802 ,M928 ,M137 ,M138 ,M143 ,M104,M134 ,M135 ,M139, M140,M180 Magnetic Pickup/Speed Sensor ,M201 ,M202 ,M203 ,M204 Magnetic Pickup Speed Sensor,M205 ,M219 ,M231 ,M233,M318 ,M319 Magnetic Pickup/Speed Sensor,M107 ,M207 ,M208 ,C101-10 ,C910-10 ,C917-10 ,HTM-801; M806 Hall Effect Magnetic Pickup/Speed Sensor ; M951 Hall Effect Magnetic Pickup/Speed Sensor 。 Dynalco temperature indicator温度指示仪型号:TMP-100 ; STM-110-11;STM-110-13 ; STM-110-14 ; TID-110; TMP-900。
  • 留言

    *详细需求:
    *手  机:
    联 系 人:
    电    话:
    E-mail:
    公  司:
    谷瀑服务条款》《隐私政策
信德迈科技(北京)有限公司 电话:010-84282935 手机:13910122694 地址: 北京朝阳区望京街10号望京SOHO-T1-C座2115室
内容声明:谷瀑为第三方平台及互联网信息服务提供者,谷瀑(含网站、客户端等)所展示的商品/服务的标题、价格、详情等信息内容系由店铺经营者发布,其真实性、准确性和合法性均由店铺经营者负责。谷瀑提醒您购买商品/服务前注意谨慎核实,如您对商品/服务的标题、价格、详情等任何信息有任何疑问的,请在购买前通过谷瀑与店铺经营者沟通确认;谷瀑上存在海量店铺,如您发现店铺内有任何违法/侵权信息,请在谷瀑首页底栏投诉通道进行投诉。